Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
conversion conversion n/a Buffer switch needs to be attached tot the buffer 6/25/2019
conversion conversion conversion - reinspect x Emergency light not working on battery backup 8/19/2018
conversion conversion conversion - reinspect x Fire service to be tested at a later date. 8/19/2018
conversion conversion conversion - reinspect x Alarm bell needs to be sound when stop switch is turned off 8/19/2018
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) x Cab emergency light and alarm bell inoperative. 6/30/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements Car top light inoperative.
MO Minimum : Elevators (S) - Fire Service 211.3a(8) Visual and audible signal x Fire service indicator light is not working, repair same. Re-inspection required 3/22/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements Replace missing pushbuttons/covers on both car operating panels
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13 - Door systems x Reversing edge on north car gate is not working, needs repair. Re-inspection required 3/22/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts Replace missing push buttons/cover in both operating panels.
MO Minimum : Elevators (S) - Fire Service 211.3a(8) Visual and audible signal x In car fire service light does not work. Repair same. Reinspection required within 90 days. 4/20/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records Maintenance Control Program records need to be up to date, including monthly fire service checks.
MO Minimum : Elevators (I) - Pits (I)1 Pit needs to be cleaned
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods Buzzer on cartop North Side has exposed wiring. Provide proper conduit/cover to enclose wiring.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates Provide signage in car in conspicuous place stating: FREIGHT ELEVATOR NO PASSENGERS, and proper class loading. All signage to be at least 1/2" tall
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Emergency communication does not work. Repair same. reinspection required within 90 days. 4/20/2023
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)12 (Re- Inspection) x Hoist ropes are at minimum diameter and need to be shortened. Replace same within 90 days. 4/20/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.9 Cleaning of Top of Cars Cartop needs to be cleaned.
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A copy of current of state certificate of operation needs to be properly displayed in machine room.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Door Systems 8.6.4.13 (Re-Inspection) x Reversing edge on North care gate is not working. Repair same. 4/20/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts Replace missing pushbuttons / covers in both panels
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x In car fire service light does not work, needs repaired. Re-inspection required within 90 days
MO Minimum : Elevators (I) - Pits (I)1 Pit needs to be cleaned
MO Minimum : Elevators (A) - Hoistways (A)16 Buzzer on car top north side has exposed wiring. Provide proper conduit / cover to enclose wiring.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates Provide signage in car in conspicuous place stating "FREIGHT ELEVATOR NO PASSENGERS" and proper class loading. All signage to be at least 1/2" tall
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)12 (Re- Inspection) x Hoist ropes are at a minimum diameter and need to be shortened, replace the same within 90 days. Re-inspection required
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.9 Cleaning of Top of Cars Cartop needs to be cleaned
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A copy of the current state operating certificate shall be displayed in the machine room
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Door Systems 8.6.4.13 (Re-Inspection) x Reversing edge on north car gate is not working, needs repaired. Re-inspection required