conversion
|
conversion
|
conversion - reinspect
|
x
|
|
Correct door for reliable operation on Phase 1 fire service.
|
12/7/2018
|
conversion
|
conversion
|
conversion - reinspect
|
x
|
|
Replace platen plate rubber isolation pad and secure properly.
|
12/7/2018
|
conversion
|
conversion
|
conversion - reinspect
|
x
|
|
Could not establish connection on emergency phone.
|
12/7/2018
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
In car emergency telephone shall work.
|
5/29/2020
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
The machine room door shall be self-closing and self-locking.
|
6/22/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022)
|
6/7/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - Door Systems 8.6.4.13 (Re-Inspection)
|
x
|
|
The door closing force exceeds 30 lbs. and shall be adjusted and re-inspected.
|
8/19/2022
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
The in car emergency telephone shall be a means of 2 way communication. The phone seems to be answered, but no one can be heard on the other end.
|
8/19/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
|
|
A current tested & tagged ABC type fire extinguisher shall be provided in the elevator machine room.
|
11/2/2022
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)5 (Machine Room Lighting)
|
|
|
The machine room lights shall be operational.
|
11/2/2022
|