Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x Emergency generator testing shall be performed. Re-inspection required 5/18/2024
A17.1-2016 : Elevators 1.17 - Standby power operation 2.27.2 x Unable to test Emergency Generator Power operation. Re-inspection required
MO Minimum : Elevators (I) - Pits (I)1 Sump pump in elevator pit is not working. Repair sump pump to remove standing water in pit
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)12 (Door open zones) x Car door restrictor shall work. Correct within 14 days. 3/31/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency phone does not work. 3/31/2020
MO Minimum : Elevators (F) - Electrical Switches (F)1 x Re-alarm in-car toggle stop switch. 3/19/2021
MO Minimum : Elevators (I) - Pits (I)1 Sump pump in elevator pit is not working. Repair sump pump to remove standing water in pit 3/11/2026
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Test is incomplete, need to perform testing of emergency generator power operation to compete inspection. Re-inspection required 3/24/2026
MO Minimum : Elevators (I) - Pits (I)1 Sump pump in elevator pit is not working. Repair sump pump to remove standing water in pit 3/24/2026