Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts No No Replace deteriorating safety rod neoprene bushings on car sling 6/5/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) Yes No Replace missing restrictor angle on the 20th floor hoistway door 1/19/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts No No Replace damaged 4x4 electrical junction box on car top and provide cover 6/5/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts No No Need to replace deteriorated safety rod bushings on both sides of the elevator 6/5/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts No No Replace damaged 4x4 electrical junction box on car top and provide cover.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) Yes No When testing the audible signaling device (alarm bell) with the 110V disconnect in the machine room in the “off” position, the device failed to sound, likely indicating that the back-up power device (battery) has failed. Repair for proper operation. Reinspection required.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) Yes No The emergency car lighting is not operational, likely indicating that the back-up power device (battery) has failed. The fixture shall be repaired to operate. Reinspection required.
MO Minimum : Elevators (K) - Car Platforms and Car Slings (K)6 No No Replace deteriorating safety rod neoprene bushings on car sling. 4/26/2021
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) Yes Yes On phase 2 fire service, the car doors would not stay open. Elevator Red-tagged and removed from service. Re-inspection required 5/20/2024
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) Yes No Need to test elevator for operation on emergency power. Re-inspection required 6/5/2026
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) Yes No Need to test elevator for operation on emergency power. Re-inspection required.
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Unit appears to have emergency generator backup power, which needs to be tested to complete inspection. Re-inspection required 2/19/2025
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No The testing has not been completed on the elevator at this time, the elevator was placed out of service. Only a machine room and hoistway inspection was performed, a full inspection shall be performed before the caregory 5 testing is completed. Reinspection is required. 5/6/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Need to test to complete Cat 5 test: test car safeties with rated load at rated speed, car buffer at rated speed with rated load, counterweight buffer at rated speed, machine brake with 125% of rated load, cab emergency lighting, alarm bell, 2 way communication, & test elevator for operation on emergency power. Re-inspection required 5/20/2024
A17.1-2016 : Elevators 2.13 - Governor, Overspeed Switch, and Seal 8.6.4.19.3 Yes No Upon performing the required five year full load, the elevator safety governor was found to have an excessive amount of pull-through force. The maximum allowed pull-through force is 925 lbs. Repair or replacement of the governor is required and a reinspection shall be performed before the elevator can be returned to service. 5/6/2024
A17.1-2016 : Elevators 3.22 - Wire rope fastening and hitch plate 8.6.3.3 Yes No The dead end hitch has a spring that is broken in the machine room that shall be replaced for the hoisting ropes to have an equal amount of tension. Reinspection required.
A17.1-2016 : Elevators 6.3 - Firefighters' service (A17.1-1984 through A17.1a-1988 and A17.3) 8.6.4.19.6 Yes No On phase 2 fire service, the car doors would not stay open. Re-inspection required in 14 days.
conversion conversion conversion - reinspect Yes No Doors closing automatically on Phase 2 11/28/2018
conversion conversion n/a No No Make appropriate repair in 2 ft. hole in wall of hatch and machine room 2/28/2019
conversion conversion n/a No No Terminal slowdown switch box cover missing. 2/28/2019
conversion conversion n/a No No Remove wiring from back wall of hoistway at 24th floor 2/28/2019