MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.3.1 Replacement Parts
|
|
|
Replace deteriorating safety rod neoprene bushings on car sling
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection)
|
x
|
|
Replace missing restrictor angle on the 20th floor hoistway door
|
1/19/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.3.1 Replacement Parts
|
|
|
Replace damaged 4x4 electrical junction box on car top and provide cover
|
|
MO Minimum : Elevators
|
(K) - Car Platforms and Car Slings
|
(K)6
|
|
|
Replace deteriorating safety rod neoprene bushings on car sling.
|
4/26/2021
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection)
|
x
|
x
|
On phase 2 fire service, the car doors would not stay open. Elevator Red-tagged and removed from service. Re-inspection required
|
5/20/2024
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Unit appears to have emergency generator backup power, which needs to be tested to complete inspection. Re-inspection required
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
The testing has not been completed on the elevator at this time, the elevator was placed out of service. Only a machine room and hoistway inspection was performed, a full inspection shall be performed before the caregory 5 testing is completed. Reinspection is required.
|
5/6/2024
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Need to test to complete Cat 5 test: test car safeties with rated load at rated speed, car buffer at rated speed with rated load, counterweight buffer at rated speed, machine brake with 125% of rated load, cab emergency lighting, alarm bell, 2 way communication, & test elevator for operation on emergency power. Re-inspection required
|
5/20/2024
|
A17.1-2016 : Elevators
|
2.13 - Governor, Overspeed Switch, and Seal
|
8.6.4.19.3
|
x
|
|
Upon performing the required five year full load, the elevator safety governor was found to have an excessive amount of pull-through force. The maximum allowed pull-through force is 925 lbs. Repair or replacement of the governor is required and a reinspection shall be performed before the elevator can be returned to service.
|
5/6/2024
|
conversion
|
conversion
|
conversion - reinspect
|
x
|
|
Doors closing automatically on Phase 2
|
11/28/2018
|
conversion
|
conversion
|
n/a
|
|
|
Make appropriate repair in 2 ft. hole in wall of hatch and machine room
|
2/28/2019
|
conversion
|
conversion
|
n/a
|
|
|
Terminal slowdown switch box cover missing.
|
2/28/2019
|
conversion
|
conversion
|
n/a
|
|
|
Remove wiring from back wall of hoistway at 24th floor
|
2/28/2019
|