Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts Replace deteriorating safety rod neoprene bushings on car sling
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) x Replace missing restrictor angle on the 20th floor hoistway door 1/19/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts Replace damaged 4x4 electrical junction box on car top and provide cover
MO Minimum : Elevators (K) - Car Platforms and Car Slings (K)6 Replace deteriorating safety rod neoprene bushings on car sling. 4/26/2021
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x x On phase 2 fire service, the car doors would not stay open. Elevator Red-tagged and removed from service. Re-inspection required 5/20/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Unit appears to have emergency generator backup power, which needs to be tested to complete inspection. Re-inspection required
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x The testing has not been completed on the elevator at this time, the elevator was placed out of service. Only a machine room and hoistway inspection was performed, a full inspection shall be performed before the caregory 5 testing is completed. Reinspection is required. 5/6/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Need to test to complete Cat 5 test: test car safeties with rated load at rated speed, car buffer at rated speed with rated load, counterweight buffer at rated speed, machine brake with 125% of rated load, cab emergency lighting, alarm bell, 2 way communication, & test elevator for operation on emergency power. Re-inspection required 5/20/2024
A17.1-2016 : Elevators 2.13 - Governor, Overspeed Switch, and Seal 8.6.4.19.3 x Upon performing the required five year full load, the elevator safety governor was found to have an excessive amount of pull-through force. The maximum allowed pull-through force is 925 lbs. Repair or replacement of the governor is required and a reinspection shall be performed before the elevator can be returned to service. 5/6/2024
conversion conversion conversion - reinspect x Doors closing automatically on Phase 2 11/28/2018
conversion conversion n/a Make appropriate repair in 2 ft. hole in wall of hatch and machine room 2/28/2019
conversion conversion n/a Terminal slowdown switch box cover missing. 2/28/2019
conversion conversion n/a Remove wiring from back wall of hoistway at 24th floor 2/28/2019