Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.9 Cleaning of Top of Cars Clean car top of cable lubricating grease & debris
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts Replace deteriorating neoprene safety rod bushings on car top
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x This elevator has a backup emergency generator power that is used in case of a power outage. This system shall be scheduled to be tested and a reinspection is required. This requirement is due to the State of Missouri adopting the A17.1 2016 version of the elevator safety code. Reinspection required.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts There is a bottom guide roller on the counterweight that is worn and shall be replaced.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts The elevator car safety rod bushings have deteriorated and require replacement.
conversion conversion conversion - reinspect x Doors closing automatically on Phase 2 8/23/2018
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency phone inoperative. 2/19/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts Replace deteriorating neoprane safety bushings on car sling. 3/1/2021
MO Minimum : Elevators (K) - Car Platforms and Car Slings (K)6 Replace deteriorating neoprene safety bushings on car sling. 4/26/2021