Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (C) - Car Enclosure: Freight (C)5 No No Install guard on elevator cab lighting. 9/17/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts No No Replace missing car light guard. 3/9/2026
MO Minimum : Elevators (C) - Car Enclosure: Freight (C)5 No No Bulbs and tubes in elevator and machine room shall be guarded to prevent breakage 3/9/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) No No A written Maintenance Control Program shall be in place to maintain the equipment in compliance with the requirements of Section 8.6 3/9/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13 - Door systems No No -Vertically Closing hoistway doors do not meet requirements to have automatically closing hoistway doors. A warning bell is required to sound at least 5 seconds before the door starts to close, and a stop switch at landing to stop and reopen the doors. A17.1 1981 Rule 112.3d 3/9/2026
MO Minimum : Elevators (I) - Pits (I)1 No No Remove oil soaked pads on the pit floor. Clean up any standing oil.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts No No Repair the bottom floor pull chain cover so that is able to be locked. 2.12.6.2.3