Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 2.37 - Pressure Switch 8.6.5.14.5 Low pressure switch does not command the elevator to stop running down when pressure is removed from the hydraulic system
A17.1-2016 : Elevators 2.32 - Control Valve 8.6.5.5.1 Examination and Maintenance Oil is leaking from the control valve. Identify and repair the source of the oil leakage.
conversion conversion n/a Repair stop switch in car. Refasten to car station panel. 10/30/2023
conversion conversion n/a Replace missing number 5 floor braille tag. 10/30/2023
conversion conversion n/a Repair broken emergency light. 10/30/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Annual Inspection incomplete. Need to perform annual relief pressure test, emergency light and alarm test, and low pressure switch test. 4/2/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency Light and Bell do not work when normal power is removed 9/26/2024