MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Annual Inspection incomplete. Need to perform annual relief pressure test, emergency light and alarm test, and low pressure switch test.
|
4/2/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency Light and Bell do not work when normal power is removed
|
9/26/2024
|
A17.1-2016 : Elevators
|
2.37 - Pressure Switch
|
8.6.5.14.5
|
|
|
Low pressure switch does not command the elevator to stop running down when pressure is removed from the hydraulic system
|
|
A17.1-2016 : Elevators
|
2.32 - Control Valve
|
8.6.5.5.1 Examination and Maintenance
|
|
|
Oil is leaking from the control valve. Identify and repair the source of the oil leakage.
|
|
conversion
|
conversion
|
n/a
|
|
|
Repair broken emergency light.
|
10/30/2023
|
conversion
|
conversion
|
n/a
|
|
|
Repair stop switch in car. Refasten to car station panel.
|
10/30/2023
|
conversion
|
conversion
|
n/a
|
|
|
Replace missing number 5 floor braille tag.
|
10/30/2023
|