Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (H) - Machine Rooms (H)1 All means of access to the elevator machine rooms shall be constructed and maintained in a clear and unobstructed manner.
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) The pit light shall be operational.
MO Minimum : Elevators (A) - Hoistways (A)15 Every hoistway window opening seven (7) stories of less on an outside wall above a thoroughfare and every such window three (3) stories or less above a roof of the building or of an adjacent building shall be guarded to prevent entrance by fire or emergency rescue persons. Each such window shall be marked "Hoistway" in a readily visible manner.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022)
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers A current tested & tagged ABC type fire extinguisher shall be provided in the elevator machine room.
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be obtained and displayed in the elevator machine room.
conversion conversion n/a Emergency light in car doesn't work 12/9/2020
MO Minimum : Elevators (N) - Guide Rails (N)1 x Multiple rail brackets are loose and missing hardware. Elevator Red Tagged. 9/10/2021
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) Repair Pit light fixture to be operational
MO Minimum : Elevators (I) - Pits (I)1 The pit shall be kept clean and dry. Remove the oil from the pit floor.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.5 Code Data Plate A code data plate shall be provided.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) A code compliant MCP and all the on-site documentation required shall be provided in the machine room.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers The fire extinguisher in the machine room is out of date.
MO Minimum : Elevators (A) - Hoistways (A)15 Every hoistway window opening seven (7) stories or less on an outside wall above a thoroughfare and every such window three (3) stories or less above a roof of the building or of an adjacent building shall be guarded to prevent entrance by fire or emergency rescue persons. Each such window shall be marked “hoistway” in a readily visible manner.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates Provide Hall Station Pictograph at each landing instructing occupants that “In case of Fire. Elevator is out of Service”
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x The emergency phone shall work. Note: The phone calls out, the other person can hear, but we cannot hear them.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency Phone in car fails to establish two-way communication 5/4/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) x x The emergency alarm, light, and phone shall be operational. Elevator Red Tagged. 9/10/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency Phone in car fails to establish two-way communication 4/11/2023