ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Phone failed
|
8/16/2019
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Must make emergency phone operable.
|
5/26/2023
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Must make Emergency Phone operable. 8.6.4.15
|
6/12/2023
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Must make emergency phone operable. 8.6.4.15
|
11/22/2023
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Must make emegency phone operable. 8.6.4.15
|
6/6/2024
|
A17.1-2016 : Elevators
|
2.2 - Headroom
|
8.11.3.1.2(c)
|
|
|
Must Maintain 84" clear head height in Mach Room. (Recently add conduits at 5'-10"must be removed from the Machine room.)
|
6/27/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.2 Headroom
|
8.11.2.1.2(b)
|
|
|
Must remove or relocate 2-3" conduits above/ Infront of Controller to maintain 7'clear headed height.
|
6/27/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.2 Headroom
|
2.7.4
|
|
|
Must remove 3" conduit in machine room at 5'-11" height must maintain clear 7" head height in Machine room. 2.7.4
|
6/21/2023
|
A17.1-2016 : Elevators
|
2.7 - Fire Extinguisher
|
8.6.1.6.5
|
|
|
Must provide current Annual test tag on Machine room Fire Extinguisher. ( currently tagged 5/21)
|
6/27/2023
|
A17.1-2016 : Elevators
|
2.7 - Fire Extinguisher
|
8.11.3.1.2(j)
|
|
|
Must Provide current Test tag on Mach room Fire Extinguisher.
|
6/27/2023
|
conversion
|
conversion
|
n/a
|
|
|
Phone Failed
|
8/3/2020
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Must post current State operating Cert. in Mach. room
|
6/27/2023
|
A17.1-2016 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Must post Current State operating Cert. in Machine room. 5.100(2)
|