Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 2.7 - Fire Extinguisher 1206.1h The fire extinguisher is expired.
MO Minimum : Elevators (H) - Machine Rooms (H)2 The machine room door shall be self-closing, self-locking and shall be operable from the interior space without the use of a key. The door does not lock.
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits The pit light shall be operational.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates Firefighters phase one instructions shall be posted near the phase one key-switch in the hallway at the egress floor.
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) The machine room lighting shall be guarded.
A17.1-1996 : Elevators 2.6 - Ventilation 101.5b The machine room temperature shall be kept within the manufacturers recommended range. The air conditioner is not working.
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)1(A) The suspension ropes shall be tagged as specified CSR 40-5.065 (L)1
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) The machine room lighting shall be guarded.
A17.1-1996 : Elevators 3.23 - Suspension rope 1001.2(c)(29) x The counterweight buffer is compressed more than 25% before the elevator car reaches the final limit. The suspension ropes shall be shortened. Unit was locked out of service by maintenance company. 9/12/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x The hoistway switches were checked and fire service was tested. All other annual inspection items and category 5 testing items still remain and shall be tested to complete the inspection. 9/12/2022
A17.1-1996 : Elevators 2.1 - Access to machine space 1001.2(b)(1) In the stairway leading up to the roof where the machine room is located there is a step that has a significant crack from end to end. Once on the roof there are also other steps that are damaged. These steps shall be repaired to provide safe and convenient access to the machine room. 8/24/2023
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 8/24/2023
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate There is no state operating certificate displayed in the machine room. 10/10/2023
A17.1-1996 : Elevators 1.13 - Emergency exit 204.1e x The car-top emergency exit shall be secured to prevent it from falling down the hoistway. If a chain is used to secure it, it shall be not more than 12 inches in length and have a factor of safety of not less than 5. 8/7/2024
A17.1-1996 : Elevators 1.13 - Emergency exit 204.1e x The emergency exit cover shall be kept locked and only be openable from the top of the car, where it shall be openable without the use of special tools. 8/7/2024