Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 2.14 - Code data plate 8.6.1.5 x Provide a code data plate. The data plate shall indicate the Code to be used for inspections and tests 1/7/2025
A17.1-2016 : Elevators 1.17 - Standby power operation 2.27.2 x Need to test emergency power operation with 125% of the rated load. 1/7/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x Emergency light does not work when normal power is removed 1/7/2025