Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1 The pit and hoistway shall be kept free of dirt and rubbish.
A17.1-1996 : Elevators 2.5 - Housekeeping 1206.2c (Clean Car Tops) The top of car shall be kept clean and free of oil, water, dirt, and rubbish.
A17.1-1996 : Elevators 1.4 - Sills and car floor 1001.2(a)(4) The cab flooring shall be secured to prevent potential tripping hazard. 5/4/2021
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 All the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 5/4/2021
A17.1-1996 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing This elevator is equipped with an overspeed valve that in not sealed. A category 5 test shall be performed on the overspeed valve on or before the next annual inspection. The valve shall be sealed and tagged after the category 5 test. 11/9/2022
MO Minimum : Elevators (S) - Fire Service 211.8 Switch Keys Fire service keys shall be kept on-site. 11/9/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.2(a) On-Site Documentation (Up-to-Date Wiring Diagrams) Wiring diagrams shall be provided in the elevator machine room. 11/9/2022
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be obtained and displayed in the elevator machine room. 11/9/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.2 Oil Leakage Collection Water and oil appear to be in the oil leakage collection container in the pit. 12/28/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.2(a) On-Site Documentation (Up-to-Date Wiring Diagrams) Wiring diagrams shall be provided in the elevator machine room. 4/5/2024
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1206.7 The fire service log shall be documented monthly. 4/5/2024
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.5.7 Record of Oil Usage There is no oil loss log. 4/5/2024
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1 The pit shall be kept clean and free of oil and debris. Oil is collecting onto pit floor and into pit sump. 4/5/2024