Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.2(a) On-Site Documentation (Up-to-Date Wiring Diagrams) No No Wiring diagrams shall be provided in the elevator machine room. 11/9/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.2(a) On-Site Documentation (Up-to-Date Wiring Diagrams) No No Wiring diagrams shall be provided in the elevator machine room. 4/5/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.2 Oil Leakage Collection No No Water and oil appear to be in the oil leakage collection container in the pit. 12/28/2022
A17.1-1996 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing No No This elevator is equipped with an overspeed valve that in not sealed. A category 5 test shall be performed on the overspeed valve on or before the next annual inspection. The valve shall be sealed and tagged after the category 5 test. 11/9/2022
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.5.7 Record of Oil Usage No No There is no oil loss log. 4/5/2024
A17.1-1996 : Elevators 2.5 - Housekeeping 1206.2c (Clean Car Tops) No No The top of car shall be kept clean and free of oil, water, dirt, and rubbish. 5/12/2025
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1 No No The pit shall be kept clean and free of oil and debris. Oil is collecting onto pit floor and into pit sump. 4/5/2024
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1 No No The pit and hoistway shall be kept free of dirt and rubbish. 5/12/2025
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1206.7 No No The fire service log shall be documented monthly. 4/5/2024
A17.1-1996 : Elevators 1.4 - Sills and car floor 1001.2(a)(4) No No The cab flooring shall be secured to prevent potential tripping hazard. 5/4/2021
MO Minimum : Elevators (S) - Fire Service 211.8 Switch Keys No No Fire service keys shall be kept on-site. 11/9/2022
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 No No All the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 5/4/2021
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current MO State operating certificate shall be obtained and displayed in the elevator machine room. 11/9/2022
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 No No A code compliant MCP and related on-site documentation shall be provided in the machine room. Violation: (1)MCP hasn’t been updated since 3/2022 8.6.1.2.1; ; (2)No oil loss log 8.6.1.4.1(c)(1); Cited 2024, not compliant. 3/31/2026