Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 2.1 - Access to machine space 1001.2(b)(1) The machine room shall have a self-closing and self-locking door and shall be operable from the interior space without the use of a key.
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The in car emergency telephone shall be operational. 4/4/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Telephone in car doesn't work 5/11/2022
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1001.2(d)(12) x x Phase 2 fire service shall be operational. 4/4/2022
A17.1-1996 : Elevators 2.7 - Fire Extinguisher 1001.2(b)(7) An ABC type fire extinguisher with a current test tag shall be mounted convenient to the machine room door.
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 All the on site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room.
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.