Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x The elevator ADA telephone inside the elevator is not working properly. Check and repair the phone line of this phone for proper operation and passenger safety. Reinspection required. 6/29/2022
A17.1-1996 : Elevators 1.17 - Standby power operation 211.2 x Determine cause of transfer switch failure and retest transfer operation of the emergency power system. 6/10/2020
A17.1-1996 : Elevators 2.3 - Lighting and receptacles 1001.2(b)(3) Inspection code The machine room GFCI receptacle was not operational on the day of inspection. Repair receptacle for proper operation for maintenance and emergency personnel. 8/10/2020
A17.1-1996 : Elevators 2.5 - Housekeeping 1001.2(b)(5) The elevator machine room shall be cleaned of debris. There is a large amount of HVAC filters and general building maintenance items that shall be removed. 8/10/2020