A17.1-1996 : Elevators
|
2.3 - Lighting and receptacles
|
1001.2(b)(3) Inspection code
|
|
|
The machine room GFCI receptacle was not operational on the day of inspection. Repair receptacle for proper operation for maintenance and emergency personnel.
|
8/10/2020
|
A17.1-1996 : Elevators
|
2.5 - Housekeeping
|
1001.2(b)(5)
|
|
|
The elevator machine room shall be cleaned of debris. There is a large amount of HVAC filters and general building maintenance items that shall be removed.
|
8/10/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
The elevator ADA telephone inside the elevator is not working properly. Check and repair the phone line of this phone for proper operation and passenger safety. Reinspection required.
|
6/29/2022
|
A17.1-1996 : Elevators
|
1.17 - Standby power operation
|
211.2
|
x
|
|
Determine cause of transfer switch failure and retest transfer operation of the emergency power system.
|
6/10/2020
|