Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 1.17 - Standby power operation 211.2 Yes No Determine cause of transfer switch failure and retest transfer operation of the emergency power system. 6/10/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) Yes No The elevator ADA telephone inside the elevator is not working properly. Check and repair the phone line of this phone for proper operation and passenger safety. Reinspection required. 6/29/2022
A17.1-1996 : Elevators 2.5 - Housekeeping 1001.2(b)(5) No No The elevator machine room shall be cleaned of debris. There is a large amount of HVAC filters and general building maintenance items that shall be removed. 8/10/2020
A17.1-1996 : Elevators 2.3 - Lighting and receptacles 1001.2(b)(3) Inspection code No No The machine room GFCI receptacle was not operational on the day of inspection. Repair receptacle for proper operation for maintenance and emergency personnel. 8/10/2020