Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x 3) All tests shall be made in accordance with the applicable ASME code as adopted and amended by the Elevator Safety Board. Testing was not completed for 5-year testing. Ref: 5.090 (3)(A) 8/31/2020
A17.1-1996 : Elevators 1.6 - Car emergency signal 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x 1) Emergency operation of signaling devices, lighting, communication and ventilation shall be maintained. Phone not functioning on battery power. Ref: 8.6.4.15 8/31/2020
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.4.19.6 2) Firefighters’ Emergency Operation (Phase I and II) shall be tested. Ref: 8.6.4.19.6 8/31/2020
A17.1-2016 : Elevators 2.7 - Fire Extinguisher NFPA 10- 6.1.3.8.3 Installation Height 4" from floor 4) Fire extinguisher shall be on a hanger per NFPA 13 10/8/2020