MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
3) All tests shall be made in accordance with the applicable ASME code as adopted and amended by the Elevator Safety Board. Testing was not completed for 5-year testing. Ref: 5.090 (3)(A)
|
8/27/2020
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
2) All tests shall be made in accordance with the applicable ASME code as adopted and amended by the Elevator Safety Board. Testing was not completed for 5-year testing. Ref: 5.090 (3)(A)
|
8/31/2020
|
A17.1-2016 : Elevators
|
2.17 - Drive machine brake
|
8.6.4.20.10
|
x
|
x
|
3) With a load in the car in accordance with Table 8.6.4.20.4, the braking system and traction relation shall be tested to show the system can safely stop and hold the car. The car failed to safely stop and hold the car. Ref: 8.6.4.20.10(a)(3)
|
8/31/2020
|
A17.1-2016 : Elevators
|
2.7 - Fire Extinguisher
|
NFPA 10- 6.1.3.8.3 Installation Height 4" from floor
|
|
|
4) Fire extinguisher shall be in a hanger as per NFPA 13
|
10/8/2020
|
A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
1206.2a
|
x
|
|
1) Water and oil shall not be allowed to accumulate on pit floors. Ref: 8.6.4.7.4
|
8/27/2020
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
8.6.4.19.6
|
|
|
2) Firefighters’ Emergency Operation (Phase I and II) shall be tested. Ref: 8.6.4.19.6
|
8/27/2020
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
8.6.4.19.6
|
x
|
x
|
1) Firefighters’ Emergency Operation (Phase I and II) shall be tested. Ref: 8.6.4.19.6
|
8/31/2020
|