A17.1-1996 : Elevators
|
1.18 - Restricted opening of car or hoistway doors
|
111.5 Restricted Opening of Hall/Car Doors
|
x
|
|
2) The car-door or gate mechanical and electrical components shall be maintained to ensure safe and proper operation including means to restrict hoistway or car door opening. Ref: 8.6.4.13.1(l)
|
8/31/2020
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
1) Emergency operation of signaling devices, lighting, communication and ventilation shall be maintained. Phone not functioning on battery power. Ref: 8.6.4.15
|
8/31/2020
|
A17.1-2016 : Elevators
|
2.7 - Fire Extinguisher
|
NFPA 10- 6.1.3.8.3 Installation Height 4" from floor
|
|
|
Fire extinguisher shall be in a hanger per NFPA 13
|
10/8/2020
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
8.6.4.19.6
|
|
|
3) Firefighters’ Emergency Operation (Phase I and II) shall be tested. Ref: 8.6.4.19.6
|
8/31/2020
|