Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.4.19.6 3) Firefighters’ Emergency Operation (Phase I and II) shall be tested. Ref: 8.6.4.19.6 8/31/2020
A17.1-2016 : Elevators 2.7 - Fire Extinguisher NFPA 10- 6.1.3.8.3 Installation Height 4" from floor 2) Fire extinguisher shall be in a hanger per NFPA 13 10/8/2020
A17.1-1996 : Elevators 2.17 - Drive machine brake 1001.2(b)(15) x x Machine brake failed to hold 125% of rated load. Red tagged elevator. 6/18/2021