A17.1-1996 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
1206.7
|
|
|
A record of findings for firefighters' service operation, tested monthly as required by 8.6.11.1 with identification of the person(s) that performed the operation, and the date shall be available on-site.
|
|
|
A17.1-1996 : Elevators
|
1.7 - Car door or gate
|
204.4
|
x
|
|
Rear door operator, stop switch is broken and shall be repaired.
|
|
|
A17.1-1996 : Elevators
|
1.5 - Car lighting and receptacles
|
204.7a (3)(a) Standby Illumination in the car. (Re-Inspection)
|
x
|
|
The in car emergency lighting shall be operational.
|
5/27/2022
|
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone in car is not working.
|
|
|
A17.1-1996 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
Evacuation procedures for elevators by authorized persons and emergency personnel shall be available on-site.
|
|
|
A17.1-1996 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
Provide a code compliant MCP including onsite documents.
|
2/15/2021
|
|
A17.1-1996 : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.6.5.16.5 Over Speed Valve Testing
|
|
|
This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve on or before the next annual inspection. The valve shall be sealed and tagged after the category 5 test.
|
2/15/2021
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.5.7 Record of Oil Usage
|
|
|
A written record shall be kept of the quantity of hydraulic fluid added to the system and emptied from leakage collection containers and pans. The written record shall be kept in the machine room.
|
|