A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.4.19.7 (Re-Inspection)
|
x
|
|
Emergency generator testing shall be performed. Re-inspection required
|
9/23/2024
|
conversion
|
conversion
|
conversion - red tag
|
x
|
x
|
Red Tagged - Unintended movement of car on inspection. Also car off level - one
|
11/26/2018
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
The elevator developed brake issues during the testing and had to be taken out of service and repairs can be made. Items still need to be performed: 125% brake test, car buffer test and set the safeties with a full load. Re-inspection required
|
9/23/2024
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.4.19.7 (Re-Inspection)
|
x
|
|
This elevator has a backup emergency generator power that is used in case of a power outage. This system shall be scheduled to be tested and a reinspection is required. This requirement is due to the State of Missouri adopting the A17.1 2016 version of the elevator safety code. Reinspection required.
|
|