Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (D) - Brakes (D)1 x x Elevator failed load test. Did not hold 125% capacity. Removed from service for repair. 12/17/2018
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts The elevator car safety rod bushings have deteriorated and require replacement.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13 - Door systems A door restrictor bracket is missing on the bottom of the 20th floor hoistway door and shall be replaced.
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x This elevator has a backup emergency generator power that is used in case of a power outage. This system shall be scheduled to be tested and a reinspection is required. This requirement is due to the State of Missouri adopting the A17.1 2016 version of the elevator safety code. Reinspection required.
conversion conversion n/a Doors closing automatically on Phase 2 6/4/2019
conversion conversion conversion - reinspect x Telephone not working 8/23/2018