A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.4.19.7 (Re-Inspection)
|
x
|
|
This elevator has a backup emergency generator power that is used in case of a power outage. This system shall be scheduled to be tested and a reinspection is required. This requirement is due to the State of Missouri adopting the A17.1 2016 version of the elevator safety code. Reinspection required.
|
|
conversion
|
conversion
|
n/a
|
|
|
Doors closing automatically on Phase 2
|
6/4/2019
|
conversion
|
conversion
|
conversion - reinspect
|
x
|
|
Telephone not working
|
8/23/2018
|
MO Minimum : Elevators
|
(D) - Brakes
|
(D)1
|
x
|
x
|
Elevator failed load test. Did not hold 125% capacity. Removed from service for repair.
|
12/17/2018
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.2.1 Repair Parts
|
|
|
The elevator car safety rod bushings have deteriorated and require replacement.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.13 - Door systems
|
|
|
A door restrictor bracket is missing on the bottom of the 20th floor hoistway door and shall be replaced.
|
|