Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 8/28/2023
A17.1-1996 : Elevators 1.17 - Standby power operation 211.2 x Battery lowering shall work. Repair or replace. 8/22/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts Cartop has bolts (ceiling thru bolts) sticking up >2". This is a tripping hazard. 12/5/2024
A17.1-1996 : Elevators 2.7 - Fire Extinguisher 1206.1h Machine room shall have proper fire extinguisher and shall have current monthly/annual test tag. 12/5/2024
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1206.7 MCP Fire service testing must be properly documented monthly on log sheet. 12/5/2024
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate State operating certificate is expired. 12/5/2024
A17.1-1996 : Elevators 2.3 - Lighting and receptacles 1001.2(b)(3) Inspection code The machine room light switch shall be a toggle type switch. The machine room light switch shall not be motion activated type. 12/5/2024
A17.1-1996 : Elevators 2.3 - Lighting and receptacles 101.5a Lighting The machine room light switch shall be a toggle type switch. The machine room light switch shall not be motion activated. 12/5/2024
A17.1-1996 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve in 2021 or 2022. The valve shall be sealed and tagged after the category 5 test. 3/1/2022