Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Display the current state operating certificate.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 No No An ABC type fire extinguisher shall be kept in the machine room.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Display a copy of the current state operating certificate in the machine room.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.7 - Fire Extinguisher 8.11.2.1.2(g) No No An ABC type fire extinguisher shall be provided in the elevator machine room.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits No No The pit shall be kept clean and dry. Clean the pit.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 No No Provide a code compliant MCP including onsite documents.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.5 - Housekeeping 8.6.4.9 Cleaning of Car Tops No No Clean the car top.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.12 - Pipes, wiring, and ducts 8.11.2.1.3(r) No No There are pipes in the hoistway that shall be guarded or guttered.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.7 Firefighters' Emergency Operation: Operating Procedures No No Phase 1 fire service instructions shall be provided in the elevator lobby.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.9 Elevator Corridor Call Station Pictograph No No "In case of fire" signage is required at all landings.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.12 - Pipes, wiring, and ducts 2.8 No No Pipe runs entire hoistway is not allowed. Remove, enclose, or apply for a variance.
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers No No An ABC fire extinguisher with a current test tag shall be mounted in the machine room located convenient to the access door.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates No No Elevator shall be marked inside of the car as Elevator #2.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.11.1 Firefighters Emergency Operation: Monthly Testing No No A record of findings for firefighters' service operation required by 8.6.11.1 with identification of the person(s) that performed the operation shall be available on-site.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.12 - Pipes, wiring, and ducts 8.11.2.1.3(r) No No The copper pipes in the overhead shall be removed, or a variance shall be applied for and granted.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.10 - Hoistway construction 8.11.2.1.3(p) No No The penetration near the copper pipes in the overhead shall be sealed using approved material.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.11.1 Firefighters Emergency Operation: Monthly Testing No No Fire service testing log is not being properly documented.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.5 - Housekeeping 8.6.4.8 Machine Rooms and Machinery Spaces No No Machine room shall be kept clean and free of excess debris (boxes, used parts, etc).
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.6 - Ventilation 2.7.5.2 No No Provide machine room ventilation to meet OEM temperature/humidity requirements. Mini-split AC is not working, temp unit in place not sufficient for room requirements.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits No No Pit shall be kept clean. Remove excess debris.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.17 - Drive machine brake 2.24.8.4 Means for Manual Release Yes No Emergency brake release module shall be tested.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.5 - Car lighting and receptacles 8.6.4.15 Emergency Lighting Yes No Emergency lighting shall work. One of two lamps are not working.
MO Minimum : Elevators (A) - Hoistways (A)17 No No Pipes conveying liquids are not permitted in elevator hoistways.
conversion conversion conversion - reinspect Yes No In cab emergency telephone shall work. 10/18/2018
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No The alarm bell shall be operational. 1/10/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.23 - Suspension rope 8.11.2.1.3(cc)(1) Wire ropes shall be replaced Yes Yes The hoist rope has a broken lay. The hoist ropes shall be replaced. Elevator Red Tagged. 12/16/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.11 Periodic Inspection and Test. Yes No The hoist ropes need to be replaced. The elevator was red tagged. The full annual inspection and full category 5 test is still needed. 12/16/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.11 Periodic Inspection and Test. Yes No The hoist ropes have been replaced and the red tag removed. The full annual inspection and full category 5 test is still needed. 4/13/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No The following tests have yet to be performed and witnessed: rated speed buffer tests, unintended movement tests, 125% load tests, and rated speed full load safety test. 4/14/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No The following tests have yet to be performed and witnessed: rated speed buffer tests, unintended movement test in the down direction with 125%, 125% load tests, and rated speed full load safety test. 6/7/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.8 Switch Keys (Re-Inspection) Yes No Fire service phase 2 key switch does not work. Repair or replace and test. 10/18/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.17 - Drive machine brake 2.24.8.4 Means for Manual Release Yes No Emergency brake release module shall be tested. 10/18/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.5 - Car lighting and receptacles 8.6.4.15 Emergency Lighting Yes No Emergency lighting shall work. One of two lamps are not working. 10/18/2024