ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
The alarm bell shall be operational.
|
1/10/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Display the current state operating certificate.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.7 - Fire Extinguisher
|
8.6.1.6.5
|
|
|
An ABC type fire extinguisher shall be kept in the machine room.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Display a copy of the current state operating certificate in the machine room.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.7 - Fire Extinguisher
|
8.11.2.1.2(g)
|
|
|
An ABC type fire extinguisher shall be provided in the elevator machine room.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
8.6.4.7 Cleaning of Pits
|
|
|
The pit shall be kept clean and dry. Clean the pit.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
Provide a code compliant MCP including onsite documents.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.5 - Housekeeping
|
8.6.4.9 Cleaning of Car Tops
|
|
|
Clean the car top.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.12 - Pipes, wiring, and ducts
|
8.11.2.1.3(r)
|
|
|
There are pipes in the hoistway that shall be guarded or guttered.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.23 - Suspension rope
|
8.11.2.1.3(cc)(1) Wire ropes shall be replaced
|
x
|
x
|
The hoist rope has a broken lay. The hoist ropes shall be replaced. Elevator Red Tagged.
|
12/16/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.11 Periodic Inspection and Test.
|
x
|
|
The hoist ropes need to be replaced. The elevator was red tagged. The full annual inspection and full category 5 test is still needed.
|
12/16/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.11 Periodic Inspection and Test.
|
x
|
|
The hoist ropes have been replaced and the red tag removed. The full annual inspection and full category 5 test is still needed.
|
4/13/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
8.6.11.1 Firefighters Emergency Operation: Monthly Testing
|
|
|
A record of findings for firefighters' service operation required by 8.6.11.1 with identification of the person(s) that performed the operation shall be available on-site.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.12 - Pipes, wiring, and ducts
|
8.11.2.1.3(r)
|
|
|
The copper pipes in the overhead shall be removed, or a variance shall be applied for and granted.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.10 - Hoistway construction
|
8.11.2.1.3(p)
|
|
|
The penetration near the copper pipes in the overhead shall be sealed using approved material.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.8 Switch Keys (Re-Inspection)
|
x
|
|
Fire service phase 2 key switch does not work. Repair or replace and test.
|
10/18/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.17 - Drive machine brake
|
2.24.8.4 Means for Manual Release
|
x
|
|
Emergency brake release module shall be tested.
|
10/18/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.5 - Car lighting and receptacles
|
8.6.4.15 Emergency Lighting
|
x
|
|
Emergency lighting shall work. One of two lamps are not working.
|
10/18/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
8.6.11.1 Firefighters Emergency Operation: Monthly Testing
|
|
|
Fire service testing log is not being properly documented.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.5 - Housekeeping
|
8.6.4.8 Machine Rooms and Machinery Spaces
|
|
|
Machine room shall be kept clean and free of excess debris (boxes, used parts, etc).
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.6 - Ventilation
|
2.7.5.2
|
|
|
Provide machine room ventilation to meet OEM temperature/humidity requirements. Mini-split AC is not working, temp unit in place not sufficient for room requirements.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
8.6.4.7 Cleaning of Pits
|
|
|
Pit shall be kept clean. Remove excess debris.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.17 - Drive machine brake
|
2.24.8.4 Means for Manual Release
|
x
|
|
Emergency brake release module shall be tested.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.5 - Car lighting and receptacles
|
8.6.4.15 Emergency Lighting
|
x
|
|
Emergency lighting shall work. One of two lamps are not working.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.7 Firefighters' Emergency Operation: Operating Procedures
|
|
|
Phase 1 fire service instructions shall be provided in the elevator lobby.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.9 Elevator Corridor Call Station Pictograph
|
|
|
"In case of fire" signage is required at all landings.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.12 - Pipes, wiring, and ducts
|
2.8
|
|
|
Pipe runs entire hoistway is not allowed. Remove, enclose, or apply for a variance.
|
|
conversion
|
conversion
|
conversion - reinspect
|
x
|
|
In cab emergency telephone shall work.
|
10/18/2018
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)17
|
|
|
Pipes conveying liquids are not permitted in elevator hoistways.
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
|
|
An ABC fire extinguisher with a current test tag shall be mounted in the machine room located convenient to the access door.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
|
|
Elevator shall be marked inside of the car as Elevator #2.
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
The following tests have yet to be performed and witnessed: rated speed buffer tests, unintended movement tests, 125% load tests, and rated speed full load safety test.
|
4/14/2022
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
The following tests have yet to be performed and witnessed: rated speed buffer tests, unintended movement test in the down direction with 125%, 125% load tests, and rated speed full load safety test.
|
6/7/2022
|