A17.1-1996 : Elevators
|
1.18 - Restricted opening of car or hoistway doors
|
111.5 Restricted Opening of Hall/Car Doors
|
x
|
|
The car door restrictor shall be operational.
|
7/5/2022
|
A17.1-1996 : Elevators
|
1.18 - Restricted opening of car or hoistway doors
|
111.5 Restricted Opening of Hall/Car Doors
|
x
|
|
The car door restrictor shall be operational. (Prior inspection violation that has yet to be cleared).
|
10/26/2023
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
The in car emergency telephone shall be operational.
|
7/5/2022
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Two-way communication device shall work. The button lights up, but does not dial (communication loss works).
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Category 5 test is still incomplete. All parts of the category 5 test remain except the governor pullout/pullthru and governor switch/jaw.
|
10/26/2023
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Inspection is still incomplete. Still need to check pit, restrictor, and SOS.
|
10/26/2023
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Acceptance test incomplete. Remaining items: measure slide, 100% car buffer, 0% CW buffer, emergency light/alarm/phone, door pressure, phase 1 & 2 fire service, in-car stop, communication loss, runby measurement, traction loss detection.
|
11/2/2023
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
The category 5 test is incomplete. The following testing item remains: The safeties shall be set with a full load and a slide measurement shall be provided.
|
7/5/2022
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Could not test wind-up safeties. A tool to reset the car safeties shall be available on-site and the safeties shall be tested.
|
10/26/2023
|
A17.1-1996 : Elevators
|
2.1 - Access to machine space
|
1001.2(b)(1)
|
|
|
Provide code compliant machine room door handle and lock.
|
|
A17.1-1996 : Elevators
|
2.11 - Disconnecting Means and Control
|
210.4
|
|
|
110V disconnect shall be labeled. Where there is more than one machine in a room, the disconnect for each machine shall be conspicuously numbered to correspond to the machine it controls.
|
|
A17.1-2016 : Elevators
|
2.17 - Drive machine brake
|
2.24.8.3
|
x
|
|
2.24.8.4 - Emergency brake release module shall work and be retested.
|
|
A17.1-2016 : Elevators
|
2.3 - Lighting and receptacles
|
2.7.9.1
|
x
|
|
Check machine room for adequate lighting (not less than 19 fc at floor).
|
11/2/2023
|
A17.1-1996 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022)
|
|
A17.1-1996 : Elevators
|
2.7 - Fire Extinguisher
|
1001.2(b)(7)
|
|
|
An ABC type fire extinguisher shall be kept in the machine room.
|
|
A17.1-1996 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
1001.2(b)(8)
|
|
|
All pipes conveying liquid, vapor, or gas that are above or come near elevator equipment shall be guarded or guttered.
|
|
A17.1-1996 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
102.2
|
|
|
Condensation is dripping on duct. All pipes conveying liquid, vapor, or gas that are above or come near elevator equipment shall be guarded or guttered.
|
|
A17.1-2016 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
2.8.2
|
x
|
|
Machine room heat detectors failed to initiate recall or shunt (4 devices).
|
11/2/2023
|
A17.1-1996 : Elevators
|
3.8 - Top emergency exit
|
1001.2(c)(12)
|
|
|
Car top exit shall be properly secured.
|
|
A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
106.1e Illumination of Pits
|
|
|
The pit lighting shall be operational.
|
|
A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
106.1
|
|
|
Pit shall be kept clean. Remove excess debris.
|
|
A17.1-1996 : Elevators
|
5.9 - Buffers and emergency terminal speed limiting devices
|
1002.3f
|
x
|
|
The elevator makes contact with the with the car buffer every time the car reaches the bottom landing. Take corrective action.
|
7/5/2022
|
A17.1-1996 : Elevators
|
5.9 - Buffers and emergency terminal speed limiting devices
|
1002.3f
|
x
|
|
The elevator makes contact with the with the car buffer every time the car reaches the bottom landing. Take corrective action. (Prior inspection violation that has yet to be cleared).
|
10/26/2023
|
conversion
|
conversion
|
conversion - reinspect
|
x
|
|
In cab emergency telephone shall work.
|
10/18/2018
|
conversion
|
conversion
|
conversion - reinspect
|
x
|
|
Car top emergency exit must be secured to car top and shall only be able to open from the car top without the use of tools.
|
10/18/2018
|
conversion
|
conversion
|
conversion - reinspect
|
x
|
|
Car door restrictor shall work.
|
10/18/2018
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Display the current state operating certificate.
|
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
|