Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 3.8 - Top emergency exit 1001.2(c)(12) Car top exit shall be properly secured.
A17.1-1996 : Elevators 2.1 - Access to machine space 1001.2(b)(1) Provide code compliant machine room door handle and lock.
A17.1-1996 : Elevators 2.7 - Fire Extinguisher 1001.2(b)(7) An ABC type fire extinguisher shall be kept in the machine room.
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Display the current state operating certificate.
A17.1-1996 : Elevators 2.8 - Pipes, wiring, and ducts 1001.2(b)(8) All pipes conveying liquid, vapor, or gas that are above or come near elevator equipment shall be guarded or guttered.
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits The pit lighting shall be operational.
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022)
A17.1-1996 : Elevators 2.11 - Disconnecting Means and Control 210.4 110V disconnect shall be labeled. Where there is more than one machine in a room, the disconnect for each machine shall be conspicuously numbered to correspond to the machine it controls.
A17.1-1996 : Elevators 2.8 - Pipes, wiring, and ducts 102.2 Condensation is dripping on duct. All pipes conveying liquid, vapor, or gas that are above or come near elevator equipment shall be guarded or guttered.
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1 Pit shall be kept clean. Remove excess debris.
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Could not test wind-up safeties. A tool to reset the car safeties shall be available on-site and the safeties shall be tested. 10/26/2023
conversion conversion conversion - reinspect x In cab emergency telephone shall work. 10/18/2018
conversion conversion conversion - reinspect x Car top emergency exit must be secured to car top and shall only be able to open from the car top without the use of tools. 10/18/2018
conversion conversion conversion - reinspect x Car door restrictor shall work. 10/18/2018
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Category 5 test is still incomplete. All parts of the category 5 test remain except the governor pullout/pullthru and governor switch/jaw. 10/26/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Inspection is still incomplete. Still need to check pit, restrictor, and SOS. 10/26/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Acceptance test incomplete. Remaining items: measure slide, 100% car buffer, 0% CW buffer, emergency light/alarm/phone, door pressure, phase 1 & 2 fire service, in-car stop, communication loss, runby measurement, traction loss detection. 11/2/2023
A17.1-2016 : Elevators 2.3 - Lighting and receptacles 2.7.9.1 x Check machine room for adequate lighting (not less than 19 fc at floor). 11/2/2023
A17.1-2016 : Elevators 2.8 - Pipes, wiring, and ducts 2.8.2 x Machine room heat detectors failed to initiate recall or shunt (4 devices). 11/2/2023
A17.1-1996 : Elevators 1.6 - Car emergency signal 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Two-way communication device shall work. The button lights up, but does not dial (communication loss works).
A17.1-2016 : Elevators 2.17 - Drive machine brake 2.24.8.3 x 2.24.8.4 - Emergency brake release module shall work and be retested.
A17.1-1996 : Elevators 1.18 - Restricted opening of car or hoistway doors 111.5 Restricted Opening of Hall/Car Doors x The car door restrictor shall be operational. 7/5/2022
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The in car emergency telephone shall be operational. 7/5/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x The category 5 test is incomplete. The following testing item remains: The safeties shall be set with a full load and a slide measurement shall be provided. 7/5/2022
A17.1-1996 : Elevators 5.9 - Buffers and emergency terminal speed limiting devices 1002.3f x The elevator makes contact with the with the car buffer every time the car reaches the bottom landing. Take corrective action. (Prior inspection violation that has yet to be cleared). 10/26/2023
A17.1-1996 : Elevators 1.18 - Restricted opening of car or hoistway doors 111.5 Restricted Opening of Hall/Car Doors x The car door restrictor shall be operational. (Prior inspection violation that has yet to be cleared). 10/26/2023
A17.1-1996 : Elevators 5.9 - Buffers and emergency terminal speed limiting devices 1002.3f x The elevator makes contact with the with the car buffer every time the car reaches the bottom landing. Take corrective action. 7/5/2022