Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 4.1 - Car platform guard 2.15.9 Yes No 2.15.9.2(a) - Platform guard shall not be less than 48". Pit depth results in need of a retractable guard or variance approved by State Board. If variance is not approved at next board meeting, unit shall be removed from service until proper guard installed. Note: Variance was approved for car #1. 9/30/2024
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
A17.1-1996 : Elevators 2.7 - Fire Extinguisher 1001.2(b)(7) No No A current tested & tagged ABC type fire extinguisher shall be provided in the elevator machine room.
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1206.7 No No A record of findings for firefighters' service operation required by 8.6.11.1 with identification of the person(s) that performed the operation shall be available on-site.
A17.1-1996 : Elevators 1.3 - Operating control devices 1001.2(a)(3) No No All lights on the car operating panel shall be operational.
A17.1-1996 : Elevators 2.7 - Fire Extinguisher 1001.2(b)(7) No No An ABC fire extinguisher with a current test tag shall be mounted in the machine room located convenient to the access door. Note: The test tag is expired.
A17.1-1996 : Elevators 2.5 - Housekeeping 1001.2(b)(5) No No Articles or materials not necessary for the maintenance or operation of the elevator shall not be stored in the machine room.
conversion conversion conversion - reinspect Yes No Car door restrictor shall work. 10/19/2018
A17.1-1996 : Elevators 1.12 - Car enclosure 1001.2(a)(12) No No Electrical devices in the car enclosure shall have covers installed.
A17.1-1996 : Elevators 1.17 - Standby power operation 211.2 Yes No Elevators that are equipped to operate on emergency power shall be tested with no load in the car, operating on emergency power. All cars to be tested. 11/26/2024
A17.1-1996 : Elevators 1.17 - Standby power operation 211.2 Yes No Emergency power testing could not be completed due to failure of auxiliary generator to operate. Take corrective action and re-test. 1/13/2025
A17.1-1996 : Elevators 2.5 - Housekeeping 1206.2b (Clean Machine Room) No No Equipment in the machine room not being used in conjunction with the function or use of the elevator shall be removed.
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3.2 Phase I Operation Recall by Initiating Device Yes Yes Fire alternate and fire main displayed opposite. Lobby smoke sends to floor 2 and displayed as fire main. All others recall to 1 and display fire alternate. 9/30/2024
conversion conversion conversion - reinspect Yes No In cab emergency telephone shall work. 10/19/2018
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No In cab emergency telephone shall work. 5/14/2019
A17.1-1996 : Elevators 1.6 - Car emergency signal 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No In car emergency telephone shall work. 10/25/2019
A17.1-1996 : Elevators 1.18 - Restricted opening of car or hoistway doors 1001.2(a)(18) Yes No Make the door restrictor operational. 5/14/2019
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 No No Provide a code compliant MCP including onsite documents.
A17.1-1996 : Elevators 1.12 - Car enclosure 1001.2(a)(12) No No Replace the missing handrails in the elevator.
A17.1-1996 : Elevators 1.15 - sign and operating device symbols 1001.2(a)(15) No No The car identification number shall be painted on, engraved, or securely attached to the car operating panel and shall be a minimum of 1/2" in height.
A17.1-1996 : Elevators 1.3 - Operating control devices 1001.2(a)(3) No No The car operating panel car call indicator lights and the position indicator shall all be functional.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.9 Cleaning of Top of Cars No No The car top shall be cleaned.
A17.1-1996 : Elevators 1.18 - Restricted opening of car or hoistway doors 1001.2(a)(18) Yes No The door restrictor shall be operational. 2/23/2021
A17.1-1996 : Elevators 2.1 - Access to machine space 1001.2(b)(1) No No The elevator machine room door shall be self-locking and self-closing and shall only be accessible to authorized personnel.
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) Yes No The emergency lighting shall be operational. 2/23/2021
A17.1-1996 : Elevators 1.12 - Car enclosure 1001.2(a)(12) No No The exposed wiring inside the fixture on the back wall of the elevator cab interior shall be enclosed.
A17.1-1996 : Elevators 2.7 - Fire Extinguisher 1001.2(b)(7) No No The fire extinguisher is the machine room is expired and shall be replaced by a current tested fire extinguisher.
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) Yes No The in car emergency lighting shall be operational. 4/14/2022
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) Yes No The in car emergency lighting shall be operational. 1/12/2024
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No The in car emergency telephone shall be operational. 4/12/2022
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No The in car emergency telephone shall be operational. 2/23/2021
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (2)(C) Re-Inspection Required to Enforce. Yes No The machine room door shall be self-closing, self-locking and shall be operable from the interior space without the use of a key. Note: There is no machine room door at all. 4/14/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (2)(C) Re-Inspection Required to Enforce. Yes No The machine room door shall be self-closing, self-locking and shall be operable from the interior space without the use of a key. Note: There is no machine room door at all. 1/12/2024
A17.1-1996 : Elevators 2.6 - Ventilation 1001.2(b)(6) No No The machine room ventilation shall be operational.
A17.1-1996 : Elevators 1.18 - Restricted opening of car or hoistway doors 111.5 Restricted Opening of Hall/Car Doors Yes No The means to restrict opening of the car door shall be operational. 1/12/2024
A17.1-1996 : Elevators 1.18 - Restricted opening of car or hoistway doors 111.5 Restricted Opening of Hall/Car Doors Yes No The means to restrict opening of the car door shall be operational. 4/14/2022
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.5 Yes No The pit light shall work. 9/30/2024
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits No No The pit lighting shall be operational.
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits No No The pit shall be kept clean. Clean the pit.
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No The safeties shall be tested as required by A17.2, item 2.29. Note: Winding drum safety access is presently covered by glued on flooring. 4/14/2022