Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13 - Door systems Adjust upthrust roller bearings for proper clearance to door hangar track (multiple floors). 3/28/2024
MO Minimum : Elevators (I) - Pits (I)1 The pit shall be kept clean. Remove excess debris. 3/28/2024
A17.1-1996 : Elevators 1.18 - Restricted opening of car or hoistway doors 1001.2(a)(18) x Restricted opening inoperative. Repair 8/7/2019
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency light inoperative. 8/7/2019
A17.1-1996 : Elevators 2.10 - Numbering of elevators, machines, and disconnect switches 1001.2(b)(10) Mark car number on car top and corresponding governor in machine room. 11/20/2019
A17.1-1996 : Elevators 2.3 - Lighting and receptacles 101.5a Lighting Relamp machine room lights as needed, lighting to be 10fc at floor level. 3/14/2024
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits Pit runby signage located on desk in equipment room. Mount signage in a conspicuous place inside pit area. 11/20/2019