Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x 2 way communication is not working. Re-inspection required 4/20/2023
A17.1-1996 : Elevators 1.18 - Restricted opening of car or hoistway doors 1001.2(a)(18) x Restricted opening inoperative. 8/7/2019
A17.1-1996 : Elevators 1.18 - Restricted opening of car or hoistway doors 111.5 Restricted Opening of Hall/Car Doors x Door restrictor is out of adjustment, repair as needed. 8/4/2023
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) x Emergency lighting shall work. 4/15/2024
A17.1-1996 : Elevators 1.6 - Car emergency signal 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Alarm bell shall work. 4/15/2024
A17.1-1996 : Elevators 1.6 - Car emergency signal 1004.2(a)(6) (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency light inoperative. 8/7/2019
A17.1-1996 : Elevators 2.1 - Access to machine space 101.3a Provide safe and convenient access to the elevator machine room. Lights at the top of the stairwell, leading into the room have been removed. Replace. 3/14/2024
A17.1-1996 : Elevators 2.10 - Numbering of elevators, machines, and disconnect switches 1001.2(b)(10) Mark car top #3, and corresponding number on machine room control cabinet, main line disconnect switch, machine and governor. 11/20/2019
A17.1-1996 : Elevators 2.42 - Earthquake Inspection and Tests (Seismic Risk Zone 2 or Greater) 8.4.10.1.2 - Protection not functioning x Seismic feature not working correctly, repair as needed. 8/4/2023
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1001.2(d)(12) - Cab fire service light inoperative. 11/20/2019