Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 2.1 - Access to machine space 101.3d Machine room door shall be self-closing and self-locking.
A17.1-1996 : Elevators 1.4 - Sills and car floor 110.11a Adjust floor heights (car sill to floor sill) to be even. Currently 1/2" below.
A17.1-1996 : Elevators 1.18 - Restricted opening of car or hoistway doors 111.5 Restricted Opening of Hall/Car Doors x The car door restrictor shall work at all floors. 4/15/2024
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO state operating certificate shall be obtained and displayed in the elevator machine room. 6/22/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.1 Making Safety Devices Inoperative or Ineffective (Re-Inspection) x Battery lowering shall work. Battery unit has been removed, must be replaced. 8/1/2024