MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)7
|
|
|
620-85 Needs GFCI in machine room. (REINSPECTION WITHIN 30 days) Multi-year violation.
|
8/4/2021
|
A17.1-1996 : Elevators
|
2.3 - Lighting and receptacles
|
1001.2(b)(3) Inspection code
|
|
|
620.53 NEC machine room needs GFCI recepticle
|
8/4/2021
|
A17.1-1996 : Elevators
|
2.3 - Lighting and receptacles
|
1001.2(b)(3) Inspection code
|
|
|
620.85 Needs GFCI in machine room
|
8/4/2021
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
B(11)/1.6.1/ : 2-WAY COMMUNICATION DEVICE SHALL WORK(with and w/o main power) and give proper location. Dials but doesn't connect. Replace phone battery also. (REINSPECTION 14days to REDTAG)
|
8/28/2023
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)8 Car Lighting
|
|
|
Cab lighting bulbs shall be protected
|
9/20/2023
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Current State Operating Permit shall be displayed in the Equipment Room in a non-combustible frame. 2013 displayed
|
8/4/2021
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Display current state operating certificate in machine room
|
9/20/2023
|
A17.1-1996 : Elevators
|
2.7 - Fire Extinguisher
|
1001.2(b)(7)
|
|
|
Fire extinguisher has,t been checked since 2017
|
1/20/2021
|
A17.1-1996 : Elevators
|
2.7 - Fire Extinguisher
|
1001.2(b)(7)
|
|
|
Fire extinguisher has,t been checked since 2017
|
8/4/2021
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
needs current certificate posted
|
8/4/2021
|