Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (2)(C) Re-Inspection Required to Enforce. Yes No The machine room door shall be self-closing, self-locking and shall be operable from the interior space without the use of a key. Note: There is no machine room door at all. 4/17/2024
MO Minimum : Elevators (A) - Hoistways (A)13 No No The hole in the hoist-way wall at the top landing near the jamb side of the entrance shall be sealed using approved material.
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) Yes No In cab emergency telephone shall work. 5/14/2019
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) Yes No In car emergency telephone shall work. 10/25/2019
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting No No Provide guard on cab lighting.
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting No No The interior cab lights shall be operational.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) Yes No The in car emergency lighting shall be operational. 2/23/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) Yes No The in car emergency telephone shall be operational. 2/23/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements No No The fire extinguisher in the machine room is expired and shall be replaced with a current tested extinguisher.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) Yes No The in car emergency lighting shall be operational. 4/17/2024
MO Minimum : Elevators (H) - Machine Rooms (H)2 No No Equipment in the machine room not being used in conjunction with the function or use of the elevator shall be removed.
MO Minimum : Elevators (H) - Machine Rooms (H)2 No No The elevator machine room door shall be self-locking and self-closing and shall only be accessible to authorized personnel.
MO Minimum : Elevators (I) - Pits (I)1 No No The pit shall be kept clean. Clean the pit.
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) No No The pit lighting shall be operational.
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)11 No No Provide code compliant anti-spin devices at car and counterweight hoist rope hitches.
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current MO State operating certificate shall be displayed in the elevator machine room.
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records No No Provide a code compliant MCP including onsite documents.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers No No A current tested & tagged ABC type fire extinguisher shall be provided in the elevator machine room.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers No No An ABC fire extinguisher with a current test tag shall be mounted in the machine room located convenient to the access door. Note: The test tag is expired.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates No No The car identification number shall be painted on, engraved, or securely attached to the car operating panel and shall be a minimum of 1/2" in height.
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log No No A record of findings for firefighters' service operation required by 8.6.11.1 with identification of the person(s) that performed the operation shall be available on-site.
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) Yes No Elevators that are equipped to operate on emergency power shall be tested with no load in the car, operating on emergency power. All cars that were recently modernized to be tested. 9/30/2024
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) Yes No Elevators that are equipped to operate on emergency power shall be tested with no load in the car, operating on emergency power. All cars to be tested. 11/26/2024
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) Yes No Emergency power testing could not be completed due to failure of auxiliary generator to operate. Take corrective action and re-test. 1/13/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.9 Cleaning of Top of Cars No No The car top shall be cleaned.
conversion conversion conversion - reinspect Yes No No anti-spin device on hoist cables. 10/19/2018
conversion conversion conversion - reinspect Yes No In cab emergency phone shall work. 10/19/2018