Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13 - Door systems The hoistway door pick up roller on the 24th floor is deteriorated and shall be replaced.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements Replace drive sheave groove liners. 4/26/2021
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)2 x Suspension rope displacement and damage after counter weight safety application. Replace ropes and counter weight safety slide. 2/22/2019
MO Minimum : Elevators (S) - Fire Service 211.7 Firefighters Operations/Signage The fireman's emergency service phase I and II operations was tested and the following deficiency was noted: There is no fireman’s emergency service phase II instruction signage adjacent to the keyed switch in the car, as required.
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x This elevator has a backup emergency generator power that is used in case of a power outage. This system shall be scheduled to be tested and a reinspection is required. This requirement is due to the State of Missouri adopting the A17.1 2016 version of the elevator safety code. Reinspection required.
conversion conversion conversion - reinspect x Floors 2-3-4 Fire phase 2 security cutout bypass not working when at floor 2/4/2019