MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.13 - Door systems
|
|
|
The hoistway door pick up roller on the 24th floor is deteriorated and shall be replaced.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 Maintenance, Repair and Replacements
|
|
|
Replace drive sheave groove liners.
|
4/26/2021
|
MO Minimum : Elevators
|
(L) - Wire Ropes-Hoisting, Governor and Tiller
|
(L)2
|
|
x
|
Suspension rope displacement and damage after counter weight safety application. Replace ropes and counter weight safety slide.
|
2/22/2019
|
MO Minimum : Elevators
|
(S) - Fire Service
|
211.7 Firefighters Operations/Signage
|
|
|
The fireman's emergency service phase I and II operations was tested and the following deficiency was noted: There is no fireman’s emergency service phase II instruction signage adjacent to the keyed switch in the car, as required.
|
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.4.19.7 (Re-Inspection)
|
x
|
|
This elevator has a backup emergency generator power that is used in case of a power outage. This system shall be scheduled to be tested and a reinspection is required. This requirement is due to the State of Missouri adopting the A17.1 2016 version of the elevator safety code. Reinspection required.
|
|
conversion
|
conversion
|
conversion - reinspect
|
x
|
|
Floors 2-3-4 Fire phase 2 security cutout bypass not working when at floor
|
2/4/2019
|