Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) A copy of the MCP shall be kept in the machine room for each elevator
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) A written copy of the MCP shall be in the machine room for each unit
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 1206.2a x Clean oil soaked pads in pit and adjust left side jack to drain to recovery method. 9/11/2019
A17.1-1996 : Elevators 1.17 - Standby power operation 1001.2(a)(17) x Emergency battery back up system not working. Repair/replace as needed. 6/14/2022
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Emergency phone in car is not working, needs repaired. Re-inspection required
MO Minimum : Elevators (I) - Pits (I)1 Need to remove oil from pit
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 1206.2a x OIL SOAKED MATS IN PIT; LEFT OIL RECOVER LINE LEAKING INTO PIT 9/11/2019 4/2/2020
A17.1-2016 : Elevators 5.15.2 Unsealed Overspeed Valve 8.6.5.16.5 (Re-Inspect) x OSV is not sealed. Test, tag and seal upon completion. 6/14/2022
MO Minimum : Elevators (I) - Pits (I)1 Pit needs to be cleaned if oil and oil filled pads
MO Minimum : Elevators (I) - Pits (I)1 Pits to be cleaned of oil & oil filled pads
A17.1-1996 : Elevators 5.11 Plunger and Cylinder 1206.5b(4) Provide code compliant means of oil collection in pit. 6/15/2023
MO Minimum : Elevators (I) - Pits (I)1 Repair / replace non working sump pump in pit.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts Replace broken stop switch on door operator.