A17.1-1996 : Elevators 2.36 - Hydraulic Cylinders 302.3 No No Cylinder Packing leaking excessive 3/16/2021
A17.1-1996 : Elevators 1.15 - sign and operating device symbols 210.13 No No Phase ll instruction missing 3/16/2021
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Obtain and display a current state operating certificate in the machine room 4/7/2021
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1 No No Replace the burnt out light in the pit. 4/22/2022
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Obtain and display a current state operating certificate in the machine room 4/22/2022
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.1(a) No No Provide an MCP in the machine room 4/22/2022
A17.1-2016 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 No No Out of date
A17.1-2016 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Post updated certificate
A17.1-2016 : Elevators 5.15 - Overspeed Valve 8.6.5.16.5 No No 5 YEAR TEST DUE ON OSV ON OR BEFORE NEXT INSPECTION
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7 No No UNIT MISSING DROP CEILING INSERTS MUST REPLACE OF PUT PROTECTIVE TUBING OVER LIGHTING
A17.1-2016 : Elevators 2.36 - Hydraulic Cylinders 8.6.5.5 Gland Packing and Seals Yes No Repack the leaking jack packing it is excessive. 1/4/2023