A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone shall work.
|
8/16/2019
|
A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
106.1e Illumination of Pits
|
|
|
Remove water and oil from pit.
|
1/28/2021
|
A17.1-1996 : Elevators
|
1.8 - Door closing force
|
1001.2(a)(8)
|
x
|
|
The door closing force shall not exceed 30 lbs.
|
10/12/2021
|
A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
106.1e Illumination of Pits
|
|
|
The pit shall be kept clean.
|
11/29/2023
|
A17.1-1996 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022)
|
11/29/2023
|
A17.1-1996 : Elevators
|
1.8 - Door closing force
|
1001.2(a)(8)
|
x
|
|
The door closing pressure still exceeds 30 lbs. The door is timing out and stalling. Take corrective action as needed.
|
11/29/2021
|
A17.1-1996 : Elevators
|
2.5 - Housekeeping
|
1206.2c (Clean Car Tops)
|
|
|
Clean cartop.
|
|
A17.1-1996 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
1206.7
|
|
|
Fire service testing shall be documented monthly.
|
|
conversion
|
conversion
|
n/a
|
|
|
clean elevator pit
|
9/21/2019
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
New fire alarm panel in the machine room is not allowed. Either relocate outside of the room or state variance from elevator board shall be applied to allow installation.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.4.8 Cleaning of Machine Rooms and Machinery Spaces
|
x
|
|
Remove all non elevator related items from machine room. Re-inspection required
|
5/5/2023
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A copy of current state operating certificate needs to be properly displayed in machine room
|
11/29/2023
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Pit needs to be cleaned
|
11/29/2023
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)6 (Pit Lighting)
|
|
|
pit light shall work
|
11/29/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.2.1 General Maintenance Requirements Documentation
|
|
|
A written Maintenance control program shall be kept on site for each elevator
|
11/29/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.3.1 Replacement Parts
|
|
|
Cartop light bulb is burned out. replace same
|
11/29/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection)
|
x
|
|
Emergency light and alarm shall work
|
8/4/2023
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)4
|
|
|
Elevator machine room is not to be used for storage of non elevator related materials and equipment. Remove same
|
11/29/2023
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection)
|
x
|
|
Repair fire service phase 2 key switch. Not Red Tagged. 14 days to correct violation.
|
12/20/2024
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Fire service phase 2 operation shall be tested.
|
12/20/2024
|