Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency phone shall work. 8/16/2019
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits Remove water and oil from pit. 1/28/2021
A17.1-1996 : Elevators 1.8 - Door closing force 1001.2(a)(8) x The door closing force shall not exceed 30 lbs. 10/12/2021
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits The pit shall be kept clean. 11/29/2023
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 11/29/2023
A17.1-1996 : Elevators 1.8 - Door closing force 1001.2(a)(8) x The door closing pressure still exceeds 30 lbs. The door is timing out and stalling. Take corrective action as needed. 11/29/2021
A17.1-1996 : Elevators 2.5 - Housekeeping 1206.2c (Clean Car Tops) Clean cartop.
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1206.7 Fire service testing shall be documented monthly.
conversion conversion n/a clean elevator pit 9/21/2019
MO Minimum : Elevators (H) - Machine Rooms (H)2 New fire alarm panel in the machine room is not allowed. Either relocate outside of the room or state variance from elevator board shall be applied to allow installation.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.8 Cleaning of Machine Rooms and Machinery Spaces x Remove all non elevator related items from machine room. Re-inspection required 5/5/2023
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A copy of current state operating certificate needs to be properly displayed in machine room 11/29/2023
MO Minimum : Elevators (I) - Pits (I)1 Pit needs to be cleaned 11/29/2023
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) pit light shall work 11/29/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.1 General Maintenance Requirements Documentation A written Maintenance control program shall be kept on site for each elevator 11/29/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts Cartop light bulb is burned out. replace same 11/29/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x Emergency light and alarm shall work 8/4/2023
MO Minimum : Elevators (H) - Machine Rooms (H)4 Elevator machine room is not to be used for storage of non elevator related materials and equipment. Remove same 11/29/2023
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x Repair fire service phase 2 key switch. Not Red Tagged. 14 days to correct violation. 12/20/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Fire service phase 2 operation shall be tested. 12/20/2024