A17.1-1996 : Elevators
|
1.18 - Restricted opening of car or hoistway doors
|
1001.2(a)(18)
|
x
|
|
Car door restrictor shall work.
|
12/2/2020
|
A17.1-1996 : Elevators
|
1.5 - Car lighting and receptacles
|
204.7a (3)(a) Standby Illumination in the car. (Re-Inspection)
|
x
|
|
Emergency light shall work.
|
12/2/2020
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone shall work.
|
12/2/2020
|
A17.1-1996 : Elevators
|
2.7 - Fire Extinguisher
|
1206.1h
|
|
|
Fire extinguisher needs to be serviced.
|
12/31/2020
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Phone battery back up does not work.
|
4/15/2021
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)5 (Machine Room Lighting)
|
|
|
Provide machine room with code complaint lighting, none at time of inspection.THIS IS A LIFE AND LIMB HAZARD.
|
10/1/2023
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)7
|
|
|
Provide all electrical outlets in the elevator machine room to work.
|
10/1/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
|
|
Provide current tested fire extinguisher in the elevator machine room.
|
10/1/2023
|
MO Minimum : Elevators
|
(S) - Fire Service
|
211.3a(8) Visual and audible signal
|
|
|
Observed shunt relay on machine room wall is ACTIVE, determine cause, repair as needed.
|
10/1/2023
|
MO Minimum : Elevators
|
(S) - Fire Service
|
211.3a(8) Visual and audible signal
|
|
|
Observed fire panel in the lobby has ACTIVE TROUBLE indicated on panel, for elevator machine room shunt. Repair as needed.
|
10/1/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.3.1 Replacement Parts
|
|
|
.Replace missing handrails in the elevator, two (2)
|
10/1/2023
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)1
|
|
|
Car has camera, provide means to prevent public from accessing wires. Currently hanging down.
|
10/1/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection)
|
x
|
|
Emergency phone not working properly at time of inspection.
|
1/25/2024
|
A17.1-1996 : Elevators
|
3.22 - Wire rope fastening and hitch plate
|
212
|
|
|
Need to install rope data tag on car shackle
|
5/15/2024
|
A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
106.1e Illumination of Pits
|
|
|
Need to install new light bulb in pit
|
5/15/2024
|