Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No current certificate needs to be displayed 2/21/2020
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits No No I-1 Mo -min--oil and debree in pit--pit needs to be cleaned 2/21/2020
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Must Make Emergency Phone Operable. 8.6.4.15 9/18/2025
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Must make emergency phone operable. 8.6.4.15
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Must post current operating Cert. in Mach room 5.100(2) 1/11/2024
A17.1-2016 : Elevators 5.15 - Overspeed Valve 8.6.5.16.5 No No Must provide cat 5 test on or before next Annual insp. 8.6.5.16.5 1/23/2024
A17.1-2016 : Elevators 2.36 - Hydraulic Cylinders 8.6.5.5 Gland Packing and Seals Yes No Must repair/replace jacke Packing gland to limit oil loss. (pit overflow bucket was full and had been emptied in the last 30 days.) 8.6.5.5 5/29/2026
conversion conversion n/a No No needs maintance records on site 2/21/2020
conversion conversion n/a No No needs record of oil loss 2/21/2020
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.4 Instructions for Locating Maintenance Records No No No records 1/11/2024
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits No No Oil Accumulation in pit 1/11/2024
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits No No Pit must be kept free of oil. 8.6.4.7 5/29/2026
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits No No Pit needs to be cleaned--water/oil/debree 3/23/2020
conversion conversion n/a No No pit shall be clean and dry-removal of any oil on floor 2/21/2020