A17.1-1996 : Elevators
|
1.5 - Car lighting and receptacles
|
204.7
|
|
|
8.11.3.1.1(f) emergency light needs battery
|
2/21/2020
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Must make Emergency Phone Operable. 8.6.4.15
|
|
A17.1-1996 : Elevators
|
2.35 - Supply Line and Shutoff Valve
|
303
|
|
|
Shutoff valve in machine room will not close--needs replaced
|
3/23/2020
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.4 Instructions for Locating Maintenance Records
|
|
|
No Records
|
1/11/2024
|
A17.1-2016 : Elevators
|
5.15 - Overspeed Valve
|
8.6.5.16.5
|
|
|
Must perform Category 5 test on overspeed valve on or before next annual insp. 8.6.5.16.5
|
1/23/2024
|
A17.1-2016 : Elevators
|
5.15 - Overspeed Valve
|
8.6.5.16.5
|
x
|
|
Must perform Cat. 5 Full load test/insp. for Overspeed Valve within next 90 days. 8.6.5.16.5
|
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
8.6.11.1 Firefighters’ Emergency Operation Documentation
|
|
|
Post monthly fire service log in machine room
|
1/23/2024
|
conversion
|
conversion
|
n/a
|
|
|
needs record of oil usage
|
2/21/2020
|
conversion
|
conversion
|
n/a
|
|
|
rear restrictor needs adjusted or repairerd
|
2/21/2020
|
conversion
|
conversion
|
n/a
|
|
|
needs maintance record on site
|
2/21/2020
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
needs current certificarte posted
|
2/21/2020
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Must post current operating Cert. in Mach Room 5.100(2)
|
1/23/2024
|