Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
conversion conversion n/a No No Repair pit light 6/15/2020
conversion conversion n/a No No Install inspection port on pump valve 6/15/2020
conversion conversion n/a No No Replace leaking jack packing 6/15/2020
conversion conversion n/a No No Clean pit & remove oil from pit floor 6/15/2020
conversion conversion n/a No No Install year test tag on governor 6/15/2020
conversion conversion n/a No No Clean car top--oil 6/15/2020
conversion conversion n/a No No Rep[air emergency light in car 6/15/2020
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Repair emergency light in car 11/19/2020
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 102 Yes No Clean pit remove oil rom floor, repair pit liht 11/19/2020
A17.1-1996 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing Yes No OSV needs to be tested, tagged & sealed. 8/1/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) Yes No Repair phone in car 10/16/2023
MO Minimum : Elevators (I) - Pits (I)1 No No Clean pit 3/5/2026
MO Minimum : Elevators (I) - Pits (I)1 No No Clean pit. Remove oil from pit floor. repair pit light, clean oil off car top this is a reinspection item within 30 days max 3/5/2026
MO Minimum : Elevators (O) - Existing Hydraulic Elevators (O)4 No No Replace control valve discharge hose 3/5/2026
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1001.2(d)12 Yes Yes Perform monthly fire service test and post on log in machine room. 3/5/2026
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Post current state certificate in machine room 3/5/2026
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No POST CURRENT STATE CERTIFICATE IN THE MACHINE ROOM 3/5/2026
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Post current state certificate in the machine room 3/5/2026
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Post current state certificate in machine room 3/5/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.2(b) On-Site Documentation (Procedures for Inspections and Tests) No No provide testing procedures in the Maintenance control program 3/5/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.2(b) On-Site Documentation (Procedures for Inspections and Tests) No No Provide test procedures in the maintenance control procedures 3/5/2026
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 No No Post current MO State operating certificate in machine space. 3/5/2026
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log No No Perform monthly fire service test and document on the log in the machine room. Remove gage and supply valve install test port 3/5/2026
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log No No Perform monthly fire service testing and document on log in machine room 3/5/2026
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log No No Perform monthly fire service and document on log in machine room 3/5/2026