conversion conversion n/a Clean car top--oil 6/15/2020
MO Minimum : Elevators (I) - Pits (I)1 Clean pit
conversion conversion n/a Clean pit & remove oil from pit floor 6/15/2020
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 102 x Clean pit remove oil rom floor, repair pit liht 11/19/2020
MO Minimum : Elevators (I) - Pits (I)1 Clean pit. Remove oil from pit floor. repair pit light, clean oil off car top this is a reinspection item within 30 days max
conversion conversion n/a Install inspection port on pump valve 6/15/2020
conversion conversion n/a Install year test tag on governor 6/15/2020
A17.1-1996 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing x OSV needs to be tested, tagged & sealed. 8/1/2022
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log Perform monthly fire service and document on log in machine room
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log Perform monthly fire service test and document on the log in the machine room. Remove gage and supply valve install test port
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1001.2(d)12 x x Perform monthly fire service test and post on log in machine room.
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log Perform monthly fire service testing and document on log in machine room
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current state certificate in machine room
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current state certificate in machine room
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current state certificate in the machine room
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate POST CURRENT STATE CERTIFICATE IN THE MACHINE ROOM
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.2(b) On-Site Documentation (Procedures for Inspections and Tests) Provide test procedures in the maintenance control procedures
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.2(b) On-Site Documentation (Procedures for Inspections and Tests) provide testing procedures in the Maintenance control program
conversion conversion n/a Rep[air emergency light in car 6/15/2020
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Repair emergency light in car 11/19/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Repair phone in car 10/16/2023
conversion conversion n/a Repair pit light 6/15/2020
MO Minimum : Elevators (O) - Existing Hydraulic Elevators (O)4 Replace control valve discharge hose
conversion conversion n/a Replace leaking jack packing 6/15/2020