MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)4
|
|
|
Remove all the stored material from the machine room.
|
2/6/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.1 - Access to machine space
|
2.7.3.4
|
|
|
Remove the dead bolt from the machine room door and install a lever type handle with a mechanical room door lock, always locked outside never locked inside. It is to have a self closing self latching door closer. .
|
2/6/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.7 - Fire Extinguisher
|
8.6.1.6.5
|
|
|
Have the fire extinguisher re-certified it is expired.
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Must post current cert. in elev. machine room
|
|
A17.1-2016 : Elevators
|
2.4 - Machine space
|
8.6.4.8 Machine Room and Machinery Space
|
|
|
Must remove and not store non elevator related equipment in the machine room. 8.6.4.8
|
|
A17.1-2016 : Elevators
|
1.4 - Sills and car floor
|
2.11.12.1
|
|
|
Must make entrance floor flush with entrance sill to eliminate Trip hazard. 2.11.12.1.2 ( currently 5/8” lip between sill and floor)
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Have the emergency phone repaired as the incoming line is dead and call for re-inspection
|
2/12/2025
|