A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
10/22/2025
|
|
A17.1-1996 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
211.3a(8) Visual and audible signal
|
x
|
|
The firefighters service visual indicator (fire hat) in the car must illuminate when on firefighters service phase one return.
|
1/25/2024
|
|
A17.1-1996 : Elevators
|
1.17 - Standby power operation
|
211.2
|
x
|
|
The emergency/standby power shall be tested.
|
11/7/2025
|
|
A17.1-1996 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
1206.7
|
|
|
A record of findings for firefighters' service operation, tested monthly as required by 8.6.11.1 with identification of the person(s) that performed the operation, and the date shall be available on-site.
|
10/22/2025
|
|
A17.1-1996 : Elevators
|
4.2 - Hoistway doors
|
110
|
|
|
Hoistway door @4 shall be self-closing.
|
|
|
A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
106.1
|
|
|
Pit shall be kept dry. Remove rust from pit equipment, repiar/replace as needed. Apply rust prevention treatment to all pit steel, and investigate/repair water leak.
|
|
|
A17.1-1996 : Elevators
|
1.8 - Door closing force
|
1001.2(a)(8)
|
x
|
|
The door closing force shall not exceed 30 lbs.
|
10/7/2022
|
|
A17.1-1996 : Elevators
|
3.9 - Floor and emergency identification numbering
|
100.7
|
|
|
The car identification number shall be on the crosshead, at least 2" in height, and visible from the landing.
|
|
|
MO Minimum : Elevators
|
(E) - Machines
|
(E)4
|
|
|
Hoist rope tail retaining clips shall be properly spaced.
|
|