MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Post current state certificate in machine room
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.6.5.16.5 Over Speed Valve Testing
|
|
|
Full load overspeed vlave test past due 90 day max on completing test
|
8/23/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
Alarm bell not working on emergency power
|
7/31/2024
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)5
|
x
|
x
|
Gat switch not working red tagged out of service
|
7/31/2024
|
A17.1-2016 : Elevators
|
2.3 - Lighting and receptacles
|
2.8.2
|
x
|
|
Machine room is missing GFCI.
|
7/22/2025
|
A17.1-2016 : Elevators
|
2.4 - Machine space
|
2.7.1
|
x
|
|
Machine room walls have fire/smoke penetrations that shall be filled with appropriate fire caulking.
|
7/22/2025
|
A17.1-2016 : Elevators
|
2.7 - Fire Extinguisher
|
8.6.1.6.5
|
x
|
|
An ABC fire extinguisher with a current test tag shall be mounted in the machine room located convenient to the access door.
|
7/22/2025
|
A17.1-2016 : Elevators
|
2.10 - Numbering of Elevators, Machines, Controllers, and Disconnect Switches
|
3.29
|
x
|
|
Disconnects and controller shall have car numbering.
|
7/22/2025
|
A17.1-2016 : Elevators
|
2.14 - Code data plate
|
8.7.1.8
|
x
|
|
Machine room controller is missing appropriate alteration code plate.
|
7/22/2025
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.5
|
x
|
|
Pit lighting shall be at least 10fc across pit floor.
|
7/22/2025
|
A17.1-2016 : Elevators
|
5.14 - Supply Piping
|
3.19.1
|
x
|
|
Remove and properly cap previous oil line elbow fitting.
|
7/22/2025
|