Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 x An ABC fire extinguisher with a current test tag shall be mounted in the machine room located convenient to the access door. 7/22/2025
A17.1-2016 : Elevators 2.10 - Numbering of Elevators, Machines, Controllers, and Disconnect Switches 3.29 x Disconnects and controller shall have car numbering. 7/22/2025
A17.1-2016 : Elevators 2.14 - Code data plate 8.7.1.8 x Machine room controller is missing appropriate alteration code plate. 7/22/2025
A17.1-2016 : Elevators 2.3 - Lighting and receptacles 2.8.2 x Machine room is missing GFCI. 7/22/2025
A17.1-2016 : Elevators 2.4 - Machine space 2.7.1 x Machine room walls have fire/smoke penetrations that shall be filled with appropriate fire caulking. 7/22/2025
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.5 x Pit lighting shall be at least 10fc across pit floor. 7/22/2025
A17.1-2016 : Elevators 5.14 - Supply Piping 3.19.1 x Remove and properly cap previous oil line elbow fitting. 7/22/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Alarm bell not working on emergency power 7/31/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing Full load overspeed vlave test past due 90 day max on completing test 8/23/2023
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)5 x x Gat switch not working red tagged out of service 7/31/2024
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current state certificate in machine room